Proponents
say under-floor air distribution systems can cuts costs and
improve comfort. Critics cite problems. Both are right: The
difference is in the details
The
design of the modern office building is being shaped by rapidly
evolving technology. Facilities should be able to
adapt quickly to new technologies and changing business missions.
But one system has not kept pace with
the growing demands of the modern workplace: conventional cooling
technology.
Typical cooling technology used in the vast majority of office
buildings is overhead variable air volume, or VAV. With VAV,
air is supplied through metal ductwork to terminal units (also
called VAV boxes) located in the ceiling. The VAV boxes respond
to space thermostats to supply the required amount of conditioned
air, usually at 55 degrees Fahrenheit, to maintain space comfort.
Air is generally returned to the mechanical room through the
space above the ceiling, referred to as the return plenum.
The conventional approach is familiar to owners, designers and
contractors; it offers a 30-year track record and proven operational
efficiency. But there are two drawbacks. One
is low ventilation effectiveness. Because the supply
grills and the return grills are in the ceiling, there is a
certain amount of short cycling of air; in other words, the
supply air goes up the return without doing any work to cool
or ventilate the space.
The other disadvantage is the high
cost for renovations after occupancy. With the cooling
system above the ceiling, and constructed from sheet metal,
renovations routinely require the removal of ceiling systems
and the installation of new ductwork.
One alternative to the conventional
design is drawing a lot of attention: under-floor
air distribution. Though relatively new in the United States,
under-floor air distribution
has been used in Europe for 35 years.
Buildings with under-floor air distribution supply conditioned
air through a raised floor supply plenum, similar to cooling
systems in data centers. Air is supplied to the space through
floor air devices that are either manually adjusted by the occupants
or controlled automatically by room thermostats. Air is returned
from the space generally through a return ceiling plenum.
Unlike data centers that use raised
floors as high as three feet, raised floors for under-floor
air distribution range in height from 10 to 18 inches.
Usually, the raised floor plenum is also used for power and
data cabling. The complexity and the amount of data cabling
have an impact on the height of the raised floor. For example,
most buildings with under-floor air distribution and a single
level of under-floor data cable management have a 14-inch raised
floor.
Multiple
Benefits The use of under-floor air distribution
in the United States has grown from less than 1 percent of the
office market in 1995 to 6 percent in 2004, according
to the Center
for the Built Environment at the University of California -
Berkeley. Buildings with under-floor air distribution are
gaining popularity for several reasons. Occupant comfort in
buildings with properly designed under-floor air distribution
is higher than in buildings with conventional overhead cooling.
Reconfiguring a space for tenants is less costly in buildings
with under-floor air distribution. Air devices and the power
and data floor boxes are easily moved to accommodate furniture
modifications.
What's more, properly designed under-floor air distribution
systems provide more effective ventilation. Introducing supply
air at the floor and returning it at the ceiling effectively
removes contaminants from the space. Unlike conventional overhead
VAV cooling, there is no opportunity for short cycling of the
supply air. All the air has to go through the space to get to
the return.
At this point, the biggest disadvantage
of under-floor air distribution systems is that designers, owners,
tenants and contractors aren't familiar with the approach.
A building is a long-term investment, and nobody wants to experiment
with a technology they think is unproven.
Another barrier is the misperception
that buildings with under-floor air distribution are more expensive.
On the contrary, if implemented properly, buildings with under-floor
air distribution can be designed and built for virtually the
same cost as one with a conventional design. Part of the reason
is counterintuitive. When under-floor air distribution is incorporated
into a building design by an experienced team, the floor-to-floor
height can be reduced by 6 to 12 inches. In a building with
conventional overhead cooling, the floor-to-floor heights are
usually set by the beam-to-duct interface at the core wall.
Supply ductwork, return ductwork and sprinkler pipes compete
for space at the core, and generally dictate the amount of space
required above the ceiling. A typical ceiling plenum ranges
from between 20 and 24 inches below the structural beams.
With under-floor air distribution, there is no supply or return
ductwork, which allows the ceiling plenum to be compressed to
zero to 8 inches below the structural beams. With under-floor
air distribution, the return can actually be in the sidewall
of the core, eliminating the need for a return plenum.
It takes commitment by the entire team
- owner, designer and contractor - to execute an under-floor
air distribution project successfully. If a raised
floor and under-floor air distribution is an addition or alternate
to a base design, the system is doomed to failure. Integrating
under-floor air distribution in a building design affects everything
from electrical distribution to structural design. It is a complete
building type that needs to be treated as such.
Some buildings with under-floor air
distribution constructed in the past several years are performing
poorly. In one new building with under-floor air distribution,
leakage rates exceeded 70 percent of design air flow, there
was poor temperature and humidity control, and the tenants were
very dissatisfied. The problem was that the designers, contractor
and owner were new to the system. They did not understand key
principles in the design of under-floor air distribution, especially
the importance of an airtight floor plenum.
The air leaks were sealed, and the leakage rate fell below 5
percent.
Principles of Design
Other concerns have arisen about under-floor air distribution
systems. In some cases, occupants have complained about being
too cold. Conventional overhead VAV uses nominal 55-degree supply
air to maintain space conditions in the room at 72 degrees and
50 percent humidity. Cooling air to 55 degrees wrings out moisture
and keep the humidity levels acceptable.
Under-floor air distribution systems, on the other hand, use
nominal 63-degree supply air. The problem is that, if supply
air from the cooling coil in the air handling unit is at 63
degrees, not enough moisture is taken out of the air to keep
the humidity within acceptable levels.
The answer is to use a system called coil "face and bypass."
In this system, most of the air is passed through the cooling
coil and cooled to 55 degrees to wring out the moisture, but
some air bypasses the cooling coil to blend with the 55-degree
air, raising the temperature to the required 63 degrees. Outside
air should be pretreated to remove humidity to make the face
and bypass approach more effective.
The reason for the higher supply air temperature with under-floor
air distribution is occupant comfort. Years of research and
use in Europe have shown that 63 degrees is the best temperature.
Using 55-degree supply air draws occupant complaints about comfort.
It's also a mistake to use reheat to raise the supply temperature
to 63 degrees. It is not code-compliant and will result in huge
energy bills.
Another objection to under-floor air distribution systems is
that they are too quiet, so that occupants can be distracted
by overheard conversations. With under-floor air distribution,
the air is delivered at extremely low pressure and low velocity.
As such, there is none of the usual background white noise associated
with overhead VAV. If speech privacy is important, then a sound
masking system needs to be included in the tenant design. These
systems are relatively inexpensive and consist of a sound generator
and speakers spaced above the ceiling.
Concerns have been expressed about mold and other contaminants.
In our firm's experience, this has not been a problem. Of course,
the underfloor plenum must be extensively cleaned after construction,
and the cooling system must be properly designed to dehumidify
the air. Mold requires moisture or elevated humidity levels.
A leaking pipe under the floor is another potential source of
moisture. The use of leak detection systems in specific areas
is recommended.
There is also concern that under-floor air distribution poses
a life-safety risk. If smoke is developing under the floor,
it will be distributed into the space. We are not aware of any
instance where this has happened. A modern code-compliant office
building will have space smoke detectors as well as smoke detectors
in the mechanical rooms. There is some talk in the industry
about adding smoke detectors under the floor, but so far model
codes don't require them.
Making the Decision
So how does a facility executive decide if under-floor air distribution
is right for a project? The best applications are for general
office space, especially space that is reconfigured frequently.
Spaces that are not good candidates for under-floor air distribution
include kitchen and food preparation areas, laboratory space,
central storage and loading, fitness centers, dining areas and
child care centers.
For facility executives who think under-floor
air distribution might be right for a project, it is important
to seek designers and contractors with relevant experience.
It is no harder to successfully design and build an under-floor
air distribution project successfully than it is to implement
a conventional system. But it is different.
R. Steven Spinazzola, P.E., is vice president of RTKL, an
architectural and engineering firm headquartered in Baltimore
in Bond Street Wharf